- Floor configurations that can flexibly accommodate a wide variety of experimental activities
- Handling of hazardous materials / high-pressure gases for experimental use permitted
Floor Configuration
General Specifications
Water Supply
Connection provided to each unit (25–40A)
Drainage
Two drainage systems provided to each unit (laboratory drainage / general drainage)
- Laboratory drainage: 100A
- General drainage: 100A (Excludes some units)
Other
- Handling of hazardous materials / high-pressure gases for experimental use permitted
(Types and quantities subject to consultation) - P2 / BSL-2 compatible
- Door dimensions (mm): W 2,500 x H 2,500
BCP Comapatible
- 1.25 times the strength required under the New Seismic Design Standards
(Ratio of the superstructure’s ultimate lateral load-carrying capacity to the required ultimate lateral load-carrying capacity) - Dual-line extra-high-voltage (66,000 V) power receiving system
- Power supply maintained for 72 hours after a disaster (15 VA/m2 for leased areas and emergency power for common areas) (Either single-phase or three-phase)
- Water supply and drainage functions maintained for 72 hours after a disaster (common areas only)
- Critical equipment installed on 2F or above
Reinforced-concrete exterior walls, with watertight doors or flood barriers installed at entrances
Other
- Planned to obtain BELS ☆☆☆☆☆, ZEB READY, and CASBEE Kawasaki certifications
- 24-hour on-site management (Disaster Prevention Center located on 2F)
Rendering of Leased Space(Skeleton specification allowing a high degree of layout flexibility)